Asymmetrical low-voltage ride through of brushless doubly fed induction generators for the wind power generation

Long, T and Shao, S and Abdi, E and McMahon, RA and Liu, S (2013) Asymmetrical low-voltage ride through of brushless doubly fed induction generators for the wind power generation. IEEE Transactions on Energy Conversion, 28. pp. 502-511. ISSN 0885-8969

Full text not available from this repository.

Abstract

Compared with the Doubly fed induction generators (DFIG), the brushless doubly fed induction generator (BDFIG) has a commercial potential for wind power generation due to its lower cost and higher reliability. In the most recent grid codes, wind generators are required to be capable of riding through low voltage faults. As a result of the negative sequence, induction generators response differently in asymmetrical voltage dips compared with the symmetrical dip. This paper gave a full behavior analysis of the BDFIG under different types of the asymmetrical fault and proposed a novel control strategy for the BDFIG to ride through asymmetrical low voltage dips without any extra hardware such as crowbars. The proposed control strategies are experimentally verified by a 250-kW BDFIG. © 2012 IEEE.

Item Type: Article
Uncontrolled Keywords: AC generators doubly fed induction generators (DFIG) fault ride-through wind energy
Subjects: UNSPECIFIED
Divisions: Div B > Electronics, Power & Energy Conversion
Depositing User: Cron Job
Date Deposited: 07 Mar 2014 11:46
Last Modified: 08 Dec 2014 02:17
DOI: 10.1109/TEC.2013.2261818